Ceiling-Suspended-Laminar-Air-Flow

KleenFlo Ceiling Suspended Laminar Air Flow (CLAF) is used for Pharma filling, operation theatre & packing line etc. CLAF provides ultra clean sterile HEPA filtered CLASS 100 air in an isolated area where the highly sensitive process activities are carried-out. KleenFlo LAF is available in complete stainless steel construction or GI construction with PU coated finish. The Laminar Air Flow is equipped with Minipleat Hepa with dynamically balanced ultra-low noise blowers for optimum airflow. Differential pressure monitoring is done through Magnehelic gauges. Various sizes can be manufactured and supplied to suit the specific site conditions.

Description

MODEL KFCS-36-24 KFCS-72-36
Work Area Dimension (L x W x H) 1035x760x665 MM 1950x1065x665 MM
Hepa Filter Area (L X W) 915 x 610 MM 1830 x 915 MM
Air cleanliness ISO Class 5 (ISO 14644-1:1999 (E))
Air Velocities 0.45 ± 0.05 mps
Air Flow Vertical
Noise Level Less than 67 dB
Vibration Level Minimum
Light intensity > 300 lux
Power Supply 230V AC 1-Ø 50HZ
Two Stage filtration •   EU6 – Prefilter (95% down to 5 micron)
•   EU14 – HEPA Filter (99.999% down to 0.3 micron) at supply position
Motor-blower Statically & Dynamically balanced Motor-blower with suspension arrangement to reduce noise level
Work Table SS work table with due reinforcement
Side panels Glass side panels
Lights Fluorescent Lights with Milky White Diffuser
Pressure Gauge Differential Pressure Gauge
Timer Clean Down Timer with Operation Hold indicator
DOP Test Port
5/15 Amp Switch Socket for external equipment
 

 

Options & Accessories

1.      Front doors (hinged/pneumatic cylinder)

2.      U. V. Light with Hour Meter

3.      Air / Gas Cock

4.      Night Mode Operation

5.      Filter blocked alarms (audible and visible)

6.      Velocity display with alarms (audible and visible)

7.       Explosion proof electrics for Flame-proof applications